{"gross_floor_m2":84.04925200000001,"stories":2,"required_x_cm_per_m2":29.0,"actual_x_cm":5834.75,"required_x_cm":1408.7272000000003,"required_y_cm_per_m2":29.0,"actual_y_cm":4398.0,"required_y_cm":1408.7272000000003,"balance_x":0.8472749171936165,"balance_y":0.7631132917038359,"pass":true,"messages":["壁量計算 OK (X: 5835/1409cm, Y: 4398/1409cm)","N値推定: 端部柱最大 12.1 kN → 推奨金物: ホールダウン金物 HD-B15","計算仮定: 軽い屋根+2階建て係数29 cm/m² (令第46条 表3)、壁倍率は構造用合板2.5/筋交2.0/IFCWALLSTANDARDCASE1.5/汎用1.0 の簡易判定。N値は端部柱の保守側推定。層間変形角は弾性域で 1/(200×剛性比) で近似。実際の構造設計では各柱位置で個別計算 + 構造一級建築士の検証必須。","4号特例廃止 (2025-04-01) 区分: 新2号建築物 (壁量+N値+柱小径+横架材スパン) — 延べ床84.0㎡ / 2階建て"],"n_value_max_kn":12.144200000000001,"joint_recommendation":"ホールダウン金物 HD-B15","story_drift_ratio":0.0016015543428831288,"story_drift_pass":true,"asd":null}