{"gross_floor_m2":101.805192,"stories":1,"required_x_cm_per_m2":21.0,"actual_x_cm":8011.5,"required_x_cm":2137.909032,"required_y_cm_per_m2":21.0,"actual_y_cm":6282.5,"required_y_cm":2137.909032,"balance_x":0.7683943457774556,"balance_y":0.6896551724137931,"pass":true,"messages":["壁量計算 OK (X: 8012/2138cm, Y: 6282/2138cm)","N値推定: 端部柱最大 12.7 kN → 推奨金物: ホールダウン金物 HD-B15","計算仮定: 軽い屋根+2階建て係数29 cm/m² (令第46条 表3)、壁倍率は構造用合板2.5/筋交2.0/IFCWALLSTANDARDCASE1.5/汎用1.0 の簡易判定。N値は端部柱の保守側推定。層間変形角は弾性域で 1/(200×剛性比) で近似。実際の構造設計では各柱位置で個別計算 + 構造一級建築士の検証必須。","4号特例廃止 (2025-04-01) 区分: 新3号建築物 (審査省略可) — 延べ床101.8㎡ / 1階建て"],"n_value_max_kn":12.725649,"joint_recommendation":"ホールダウン金物 HD-B15","story_drift_ratio":0.0017014795320334265,"story_drift_pass":true,"asd":null}